Cable Ampacity Calculator

Okonite (US) and NEC (US code) ampacity, side by side, with Japanese (JIS) cable-size equivalents

Cable parameters

Voltage and conductor size are required. Everything else is optional — leave it blank and the result shows the full range across every applicable table configuration.


Configuration diagram

Results below update live as you change fields — no need to click a button.

Enter a voltage and conductor size to see results — they'll update live as you go.

Reference: correction factor tables

Okonite Tables 6-1 through 6-4 — used automatically whenever you set an ambient temperature and/or a cable/conduit group size above. Shown here in full for reference and verification.

Table 6-1 — Correction factors for various ambient air temperatures (base 40°C) —
Conductor temp.30°C35°C40°C45°C50°C
75°C0.970.920.860.790.72
85°C1.061.010.960.900.84
90°C1.101.051.000.950.89
100°C1.171.121.081.030.98
105°C1.201.161.111.071.03
110°C1.231.191.151.111.06
125°C1.311.271.241.201.16
130°C1.331.301.271.231.19
140°C1.381.351.321.281.25

Applies to in-air and in-conduit-in-air installs (Tables 6-20 through 6-24). This calculator interpolates between columns for the 90°C and 105°C rows.


Table 6-2 — Correction factors for various ambient earth temperatures (base 20°C) —
Conductor temp.10°C15°C20°C25°C30°C
75°C0.990.950.910.870.82
85°C1.041.020.970.930.89
90°C1.071.041.000.960.93
100°C1.121.091.051.020.98
105°C1.141.111.081.051.01
110°C1.161.131.101.071.04
125°C1.221.191.161.141.11
130°C1.241.211.181.161.13
140°C1.271.241.221.191.17

Applies to underground duct-bank and direct-burial installs (Tables 6-5 through 6-19). This calculator interpolates between columns for the 90°C and 105°C rows.


Table 6-3 — Group correction factors: number of cables in air —
Vertical \ Horizontal123456
11.000.930.870.840.830.82
20.890.830.790.760.750.74
30.800.760.720.700.690.68

Applies when cables are on a messenger/support in air (Tables 6-20 through 6-22), spaced no more than one cable diameter apart. Based on a single isolated cable at 1.00.


Table 6-4 — Group correction factors: number of conduits in air —
Vertical \ Horizontal123456
11.000.940.910.880.870.86
20.920.870.840.810.800.79
30.850.810.780.760.750.74

Applies when conductors run in isolated conduits in air (Tables 6-23, 6-24), spaced no more than one conduit diameter apart. Based on a single isolated conduit at 1.00.